Are there alternate lugs for HCM14486 to accept (3) 4/0 per phase?
Issue:
Requesting alternate lugs for HCM14486 that would accept 3 wires per phase, 4/0 each.

Product Line:
Panelboards

Environment:
I-line, accessories, Lugs

Cause:
Contractor pulled incorrect wire and is looking for an optional set of lugs.

Resolution:
Due to wire bending space in this interior, only 2 wires per phase is acceptable.  (2) #2 - 500mcm per phase.