How can we help you today?

The Write_Var instruction requires an Array of INT for the EMIS input. How do I move UINT values to a remote device?

Issue:

The Write_Var instruction requires an Array of INT for the EMIS input. How do I move UINT values to a remote device?

Product Line:

Write_var, M340, Control Expert

Resolution:

You simply need to convert the UINT to INT with the UINT_TO_INT block and move the result to the EMIS array.
If the receiving device does not automatically see the data as UINT you would need to use the INT_TO_UINT block
to see the value correctly.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings