{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Will VR breakers interrupt 5 amps and below chop current?
Issue:
Will VR breakers interrupt 5 amps and below chop current?

Product Line:
Metal Clad

Environment:
Application

Cause:
Can disregard SPD protection

Resolution:
The average chop current for copper-chromium contacts used in VR breakers is about 3 to 3.5 amps and the maximum is about 5 amps"

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: