How to disable SCADAPack LP default power saving mode in TelePACE Studio?

With “Controller LED Power Settings” and coil at address 1001 always energized, SCADAPack LP power savings mode will be OFF all the time (e.g. all LED-s will be all the time ON). Number 5 in register 49001 means that if power savings mode is turned ON then in 5 minutes will power savings mode will be turned OFF. In the attachment is shown what has to be done in TelePACE Studio program so that power savings mode is all the time OFF!

Schneider Electric USA

Attachment(s)
Controller LED power savings mode off.jpg [42.32 KB]