How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?
Issue:
How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?
Product Line:
I Line panelboard
Environment:
Application
Cause:
Installation
Resolution:
How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?
Product Line:
I Line panelboard
Environment:
Application
Cause:
Installation
Resolution:
-Rotate the entire interior of the panel.
- You will need to remove vertical Main and flip it 180 Deg for correct on/off handle orientation
- After flipping the interior, the panel Danger & Warning labels will be upside down. For replacements send a request to local SQ D Distributor asking them to have the Peru Plant mail out new labels