How can we help you today?

How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?

Issue:
How do you orientate an 800A Main breaker HCM I line panel to make it top fed, the breaker it will be upside down?

Product Line:
I Line panelboard

Environment:
Application

Cause:
Installation

Resolution:

-Rotate the entire interior of the panel.

- You will need to remove vertical Main and flip it 180 Deg for correct on/off handle orientation

- After flipping the interior, the panel Danger & Warning labels will be upside down.  For replacements send a request to local SQ D Distributor asking them to have the Peru Plant mail out new labels


Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings