How can we help you today?

How to save a configuration to the PMESWT0100 flash memory using the DFB?

Issue

Not possible to save a configuration to the weighing module flash memory

Product Line
M580

Resolution

To save a configuration to the flash memory of the PMESWT0100 using the DFB, make sure that you ignore the DTM configuration (Ignore_DTM_configuration= 1), then set the initialization bit to 0 before saving to the flash memory (Saving_in_flash memory =1).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings