Follow this procedure for configuring the Unity Pro LL984 network logic screen. In this example we will configure the screen to show two descriptor lines, the variable and the 984-address.



1- Go to the TOOLS tab and select PROJECT SETTINGS.
2- In the Project Settings window, select View 1 from the Network Display option.
3- Configure the following:
Line 1 = Blank
Line 2 = Blank
Line 3 = Blank
Line 4 = Descriptor 1
Line 5 = Descriptor 2
Line 6 = Variable
Line 7 = 984-Address
4- Click the APPLY button, then the OK button.
5- The LL984 Network Display View will now show the descriptors, variable and 984-address.