What are the "watts losses" or heat dissipation ratings for the ATV660 series drives?
Issue:
Needs the "watts loss" or heat dissipation ratings for the ATV660 series drives.
Product Line:
ATV660 enclosed Altivar Process Drives
Environment:
All models, all serial numbers
Cause:
Customer was unable to find information in current literature.
Resolution:
This information can be found in the user manual for the ATV660 series drive, Doc NHA91297 .
See attached file.
Input and Output Current Ratings and Dissipated Heat, Normal Duty Operation
| Vac | Rating | Drive Rating | Full Load Input Current (A) | Full Load Output Current (A) | Full Load Bypass Current (A) | Typical Dissipated Power at Rated Load (W) | |
|---|---|---|---|---|---|---|---|
| hp | kW | ||||||
| 230 | 1 | 0.7 | U07 | 2.6 | 4.6 | 4.2 | 63 |
| 2 | 1.5 | U15 | 5 | 8 | 6.8 | 100 | |
| 3 | 2.2 | U22 | 7.2 | 11.2 | 9.6 | 138 | |
| 5 | 3 | U40 | 12.9 | 18.7 | 15.2 | 226 | |
| 7.5 | 5.5 | U55 | 17.1 | 25.4 | 22 | 289 | |
| 10 | 7.5 | U75 | 22.8 | 32.7 | 28 | 401 | |
| 15 | 11 | D11 | 32.9 | 46.8 | 42 | 651 | |
| 20 | 15 | D15 | 45.5 | 63.4 | 54 | 768 | |
| 25 | 18 | D18 | 54.5 | 78.4 | 68 | 860 | |
| 30 | 22 | D22 | 64.3 | 92.6 | 80 | 972 | |
| 40 | 30 | D30 | 88.6 | 123 | 104 | 1231 | |
| 50 | 37 | D37 | 107.8 | 149 | 130 | 1553 | |
| 60 | 45 | D45 | 130.4 | 175 | 154 | 1789 | |
| 208 | 1 | 0.7 | U07 | 3 | 4.6 | 4.6 | 69.93 |
| 2 | 1.5 | U15 | 5.9 | 8 | 7.5 | 111 | |
| 3 | 2.2 | U22 | 8.4 | 11.2 | 10.6 | 153.18 | |
| 5 | 3 | U40 | 15 | 18.7 | 16.7 | 250.86 | |
| 7.5 | 5.5 | U55 | 20 | 25.4 | 24.2 | 320.79 | |
| 10 | 7.5 | U75 | 27 | 32.7 | 30.8 | 445.11 | |
| 15 | 11 | D11 | 39 | 46.8 | 46.2 | 722.61 | |
| 20 | 15 | D15 | 53 | 63.4 | 59.4 | 852.48 | |
| 25 | 18 | D18 | 67 | 78.4 | 74.8 | 954.6 | |
| 30 | 22 | D22 | 76 | 92.6 | 88 | 1078.92 | |
| 40 | 30 | D30 | 105 | 123 | 114 | 1366.41 | |
| 460 | 1 | 0.7 | U07 | 1.3 | 2.2 | 2.1 | 60 |
| 2 | 1.5 | U15 | 2.6 | 4 | 3.4 | 84 | |
| 3 | 2.2 | U22 | 3.8 | 5.6 | 4.8 | 115 | |
| 5 | 3 | U40 | 6.7 | 9.3 | 7.6 | 173 | |
| 7.5 | 5.5 | U55 | 9.1 | 12.7 | 10 | 231 | |
| 10 | 7.5 | U75 | 11.9 | 16.5 | 14 | 272 | |
| 15 | 11 | D11 | 17 | 23.5 | 21 | 378 | |
| 20 | 15 | D15 | 23.3 | 31.7 | 27 | 515 | |
| 25 | 18 | D18 | 28.9 | 39.2 | 34 | 680 | |
| 30 | 22 | D22 | 34.4 | 46.3 | 40 | 739 | |
| 40 | 30 | D30 | 45.9 | 61.5 | 52 | 898 | |
| 50 | 37 | D37 | 57.3 | 74.5 | 65 | 1072 | |
| 60 | 45 | D45 | 69.1 | 88 | 77 | 1324 | |
| 75 | 55 | D55 | 84.2 | 106 | 96 | 1418 | |
| 100 | 75 | D75 | 112.7 | 145 | 124 | 1823 | |
| 125 | 90 | D90 | 135.8 | 173 | 156 | 2120 | |
| 150 | 110 | C11 | 195 | 211 | 180 | 2530 | |
| 200 | 130 | C13 | 232 | 250 | 240 | 3150 | |
| 250 | 160 | C16 | 277 | 302 | 302 | 4030 | |
| 300 | 200 | C20 | 349 | 370 | * | 4380 | |
| 400 | 250 | C25 | 432 | 477 | * | 5750 | |
| 500 | 310 | C31 | 538 | 590 | * | 7810 | |
| 600 | 400 | C40 | 681 | 730 | * | 9900 | |
| 700 | 500 | C50 | 846 | 900 | * | 13330 | |
| 900 | 630 | C63 | 1058 | 1140 | * | 16250 | |
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.