What are the MCC Conversion and CNOMO accessories for PowerPacT H, J, and L breakers?
Issue:
MCC Conversion Accessory

Product Line:
Circuit Breakers

Environment:
Powerpact H, J, L

Resolution:
The MCC Conversion Accessory (S429341 for H and J; S32606 for L) is added to the direct-mount rotary handle to add the following functions to the handle:
  • IP Degree of protection IP43, IK07. The IP is increased by a built-in gasket.
  • Door locking depending on device position.
    • The door cannot be opened if the circuit breaker is ON or in the tripped position. For exceptional situations, door locking can be temporarily disabled with a tool to open the door when the circuit breaker is closed. This operation is not possible if the handle is locked by a padlock.
    • Circuit-breaker closing is disabled if the door is open. This function can be deactivated.

Machine-tool control in compliance with CNOMO Control of a machine-tool is achieved by adding kit S32602 to the standard handle for L frame (S29342 for H, J frames is obsolete).
In addition to the standard functions, the kit offers the characteristics listed below:
  • Enhanced waterproofing and mechanical protection to IP54, IK08.
  • Compliance with CNOMO E03.81.501N.

Schneider Electric USA

Attachment(s)
MCC Conversion Accessory GHD16295AA.pdf [1.27 MB]
MCC Conversion and CONOMO.pdf [259.83 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings