Programming an Altivar Process Drive to communicate over Modbus Serial.
Issue:
How to set up Altivar Process Drive to communicate over Modbus Serial?
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar 600 and 900 Process Drive
Cause:
N/A
Resolution:
Basic Settings
- Programming on the Drive
How to set up Altivar Process Drive to communicate over Modbus Serial?
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar 600 and 900 Process Drive
Cause:
N/A
Resolution:
Basic Settings
- Programming on the Drive
- Program Communication Settings
- [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus]
- [Modbus Address] Add
- [Bd.RateModbus] tbr
- [Modbus Format] tFO
- [Modbus Timeout] ttO
- [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus]
- Program Command Settings:
- [Complete settings] [Command and Reference]
- For command speed from Network, program:
- [Ref Freq 1 Config] Fr1 - Set to [Modbus] Mdb
- [Ref 1B switching] rCb - Set to [Ref Freq Channel 1] Fr1
- [Control Mode] CHCF - Set to [Not separ.] SIM
- Video: Setting an Auto/Manual or Reference Switching on the Altivar Process Drives
- [Complete settings] [Command and Reference]
- Powercycle the drive
- Using IO Profile
- [Complete Settings] [Command and Reference] [Control Mode] - Set to IO
- Command Word - 8501
- Speed Reference Word - 8502 (Hz) and 8602 (rpm)
- 16 bit word (Bit 0, 1, 2..... 15)
- Start/Stop must turn on bit 0
- Write a 1 to start
- Write a 0 to stop
- Bit 1 to 15 are assignable like logic inputs
- Example: To assign a fault reset to bit 2 - [Fault reset] - Set to C302
- Using CIA402 (DriveCom Profile)
- Works with all assemblies
- [Control Mode] CHCF to [Not separ.] SIN or [Separate]
- Command Word - 8501
Speed Reference Word - 8502 (Hz) and 8602 (rpm) - No 16 bit word
- Start/Stop
- Sequence of values must be written to the drive
- 6, 7 and 15
- Toggle between 7 and 15 to start and stop
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.