Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What factory testing is done for Powerpact H, J, and L frame breakers?
Issue:
Production test report H J L breakers

Product Line:
Circuit Breakers

Environment:
Powerpact H, J, L frames

Resolution:
During manufacture and prior to shipping, Powerpact H, J, and L frame breakers receive the following:
  1. Visual inspection of all lugs and operating mechanisms.
  2. Secondary injection testing of all trip units.  Units must trip inside the time-current published trip curve tables.
  3. Calibration of metering features in electronic trip unit to within 2%.
Note:
A report may be ordered at the time the breaker is ordered.
A test report is not on file and is not available if not ordered with the breaker.
See attached for a sample report.

Schneider Electric USA

Attachment(s)
Powerpact H J L Test Report.pdf [161.32 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings