How Is the Analog Output Scaled on ATV312 Drives?

Article available in these languages:

Resolution:
The dO parameter determines the value represented by the analog output. Two commonly used settings are:

  • oCr – Motor Current: The maximum analog output, 20 mA or 10 V, corresponds to 2 times the drive rated current (In).
  • oFr – Motor Frequency: The maximum analog output, 20 mA or 10 V, corresponds to the tFr [Max Frequency] setting.

For other dO assignments and their corresponding scaling, refer to the ATV312 programming documentation or the attached reference image.