How to Bench Test an ATV600/ATV900 Drive Using an Undersized Motor

Article available in these languages:

Resolution

Important: The following configuration is intended for temporary bench testing and functional verification only. It must not be used as a permanent installation, as improper motor protection and motor damage may occur.

Configure the drive as follows:

1. Change the Motor Control Law

Set:

  • CTT = UF5Pt

It is not necessary to configure the five voltage/frequency points.

2. Enter Motor Nameplate Data

Set:

  • MPC (cos φ) = Motor nameplate power factor
  • FRS = Motor rated frequency (Hz)
  • UNS = Motor rated voltage

Note: Enter the motor's rated voltage, not the incoming supply voltage.

3. Do Not Run an Autotune

  • Do NOT perform an autotune while using an undersized motor.

4. Limit Motor Current

Reduce the current limit:

  • CLI = Motor full-load current (FLA), or the closest available setting

5. Disable Motor Compensation Functions

Set the following parameters:

  • UFR (IR Compensation) = 0
  • SLP (Slip Compensation) = 0
  • SPGU (Inertia Factor) = 0
  • BOA (Boost) = Inactive

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.