Issue:
Micrologic switch value when not in a detent
Product Line:
Circuit Breakers
Resolution:
When a Micrologic trip unit dial such as Ir or Ii is not in the detent, but is to the low or high side of a specific set point, the real setting value can be either the closest upper or lower value. The dials are digital, not analog, so setting it inbetween settings does not set it at a value between the detents.
In Micrologic trip units with a display, the client can check the real setting value by checking the trip unit display.
Micrologic switch value when not in a detent
Product Line:
Circuit Breakers
Resolution:
When a Micrologic trip unit dial such as Ir or Ii is not in the detent, but is to the low or high side of a specific set point, the real setting value can be either the closest upper or lower value. The dials are digital, not analog, so setting it inbetween settings does not set it at a value between the detents.
In Micrologic trip units with a display, the client can check the real setting value by checking the trip unit display.
Released for: Schneider Electric USA