How can we help you today?

Can the Towerlight XVGU be used with the HMIG5U or HMISTU?

Issue:
Cannot find any information regarding the compatibility between the HMIG5U/HMISTU and the XVGU Tower light accessory.

Product Line:
HMIG5U, HMISTU, XVGU

Resolution:
No, the XVGU cannot be used with the HMIG5U nor the HMISTU. The only HMI's that can use the XVGU are the XBTGT, HMIGTO, and HMIG3U.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.