How can we help you today?
What is the Current Threshold at which the Altivar Process drive trips on SCF3 fault?
Resolution:
The SCF3 fault is triggered when the drive detects an excessive imbalance in the output currents of the three motor phases.
Specifically, the drive will trip on an SCF3 fault when the calculated differential current between the three output phases exceeds 25% of the inverter's nominal current.
When this threshold is reached, the inverter is automatically switched off and the SCF3 fault is generated to protect the drive and motor system.
An SCF3 fault may indicate conditions such as:
- Motor phase imbalance
- Output wiring issues
- Ground faults
- Motor insulation problems
- Damaged motor or drive components
If an SCF3 fault occurs, inspect the motor, output cabling, and drive installation to identify the source of the current imbalance before restarting the system.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.