How can we help you today?

What is the part number for the ATV630 Flange mounting kit?

Issue:
Flange mounting kit part number for ATV630.

Product line:
ATV630, Altivar Process

Environment:
All models.

Resolution:
The flange mount kit is based on the ATV630 part number.  See the following spreadsheet for selection.

See attachment

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

Schneider Electric USA

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.