How do you set up preset speeds on the Altivar 630 Process drive using the Somove Software?
Issue:
Can I use SoMove to set up preset speeds on the ATV630 drive?
Resolution:
- Open Somove file
First option:
- Go to Parameter Layout
- Preset Speeds
- PS2, assign to a Digital Input
- SP2 set to the desired speed.
Second option:
- Go to Parameters List
- Generic Functions
- Preset speeds
- PS2, assign to a Digital Input
- SP2 set to the desired speed.
You can assign up to 16 Preset Speeds depending on the truth table below:
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: