How can I read the mains voltage of an ATV212 drive over Modbus?

Resolution:

The mains voltage can be monitored using parameter FE04, which is available at Modbus address 65028.

The value returned by FE04 represents the mains voltage as a percentage of the drive's rated voltage.

To calculate the actual mains voltage:

Mains Voltage = (FE04 value ÷ 10,000) × Drive Rated Voltage

For example, on an ATV212...N4 drive rated for 400 V:

  • FE04 = 10570
  • This corresponds to 105.7% of the rated voltage.
  • Mains voltage = 1.057 × 400 V = 422.8 V, or approximately 423 V.

Therefore, an FE04 reading of 10570 on a 400 V ATV212 indicates a mains voltage of approximately 423 V.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.