What is the inrush for an EX112T212H?
Issue:
Inrush for EX112T212H
Product Line:
Low voltage Transformer
Environment:
Products sold in North America
Resolution:
The inrush of an EX112T212H is 5.8 times the Full Load Amperage (FLA) of the Primary. The Primary FLA (at 208V) is 312A. 312A x 5.8 = an Inrush of 1,809A
Inrush for EX112T212H
Product Line:
Low voltage Transformer
Environment:
Products sold in North America
Resolution:
The inrush of an EX112T212H is 5.8 times the Full Load Amperage (FLA) of the Primary. The Primary FLA (at 208V) is 312A. 312A x 5.8 = an Inrush of 1,809A