How can we help you today?
Unable to add data log viewer to a Vista diagram
Issue
When attempting to add additional data log viewers to a Vista diagram, the diagram will not save.
Product Line
Power Monitoring Expert 8.1
Environment
Vista
Cause
The diagram has reached the maximum number of data log viewer objects allowed. This limit is 60 data log viewer objects per diagram.
Resolution
1.)Apply hotfix available at FA293828 that increases the limit from 60 to 100 data log viewer objects per diagram.
2.) Install service pack 2 to bring the system up to PME 8.2
3.) Upgrade to PME 9.0. Please contact Technical Support for purchasing options.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.