On which side of an I-Line bus stack can a Surgelogic SPD unit be installed?

Product Line:
Surge Protective Devices (SPDs)

Environment:
IMA

Resolution:

The SPD unit requires 13.5 inches of mounting space compatible with J-frame circuit breakers. When installed on the wide side of the I-Line bus stack, three HLW4BL 4.5-inch extension brackets are necessary to accommodate the required spacing. Refer to the Surgelogic I-Line instruction bulletin for detailed installation guidelines.

https://www.se.com/us/en/download/document/8222-0015/