Video: How to change the date and time on a SEPAM 40 series relay using SFT2841.

Issue:
Need to change the date and time on the SEPAM 40 relays using SFT2841 software

Product Line:
SEPAM 40 series Relays

Environment:
SFT2841 Software

Resolution:



Step 1. Connect to the SEPAM 40 relay with SFT2841 Software,

Image

Step 2. Click on the Wrench Icon label SEPAM Diagnosis
Select The Diagnosis tab. Click on the square with 3 dots next to the date and time as shown below.

Image

Step 3. Change the Date and Time as shown below and press Apply
It will ask for a password and the default password is 0000 then press OK

Image