How to set PC system time from Vijeo citect without going to windows Environment ?
Copy below script in Cicode editor and call function from button on page. Once form is displayed, you may change the system date time manually.
Timeset() cicode function is used to set system time from scada. Read help for more info on this function.
FUNCTION
SETPC_Time()
STRING Timevar,sdate,stime;
INT hform;
hform = FormNew("Set Date/Time",35,5,1);
FormInput(0,0,"Enter Date ",sdate,10);
FormInput(0,1,"Enter Time ",sTime,10);
FormButton(2,2," OK ",0, 1);
FormButton(15,2," CANCEL ",0,2);
FormPrompt(1,3,"Note : Enter Date in DD/MM/YY format");
FormPrompt(1,4,"Note : Enter time in HH:MM:SS format");
FormGetData(hform);
FormRead(0)= 0;
TimeSet((StrToTime(stime) + StrToDate(sdate)));
END
Note :- Make sure that Regional DATE and TIME settings in PC is set to DD/MM/YY & HH:MM:SS format. Else above code will fail to set date and time.
Timeset() cicode function is used to set system time from scada. Read help for more info on this function.
FUNCTION
SETPC_Time()
STRING Timevar,sdate,stime;
INT hform;
hform = FormNew("Set Date/Time",35,5,1);
FormInput(0,0,"Enter Date ",sdate,10);
FormInput(0,1,"Enter Time ",sTime,10);
FormButton(2,2," OK ",0, 1);
FormButton(15,2," CANCEL ",0,2);
FormPrompt(1,3,"Note : Enter Date in DD/MM/YY format");
FormPrompt(1,4,"Note : Enter time in HH:MM:SS format");
FormGetData(hform);
FormRead(0)= 0;
TimeSet((StrToTime(stime) + StrToDate(sdate)));
END
Note :- Make sure that Regional DATE and TIME settings in PC is set to DD/MM/YY & HH:MM:SS format. Else above code will fail to set date and time.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.