How can we help you today?
Do the Altivar Process Drives come with a DC choke or Line Reactor?
Issue:
DC choke or Line Reactor included on Process Drives?
Product Line:
Altivar Process Drives (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drives
Cause:
N/A
Resolution:
All Altivar Process Drives come standard with DC chokes.
There is no need for a line reactor.
ATV...M3 (208/240 Vac)
Double DC choke up to Frame Size 3
Single DC choke for Frame Size 4 and upwards
ATV....N4 (400/480 Vac)
Double DC choke up to Frame Size 4
Single DC choke for Frame Size 5 and upwards
All Drive Systems and Floor Standing Products have as standard embedded line chokes and optional motor chokes.
DC choke or Line Reactor included on Process Drives?
Product Line:
Altivar Process Drives (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drives
Cause:
N/A
Resolution:
All Altivar Process Drives come standard with DC chokes.
There is no need for a line reactor.
ATV...M3 (208/240 Vac)
Double DC choke up to Frame Size 3
Single DC choke for Frame Size 4 and upwards
ATV....N4 (400/480 Vac)
Double DC choke up to Frame Size 4
Single DC choke for Frame Size 5 and upwards
NOTE:
The Size 7 ATV630 product and the Size 7A and 7B ATV930 products come standard with the DC Choke, but can be ordered without the DC Choke by adding a suffix MN to the part number.
When not using the DC Choke a 5% input line reactor or line choke MUST be used.
Example: ATV630C22N4 includes a DC Choke ATV630C22N4MN does not include a DC Choke.
Drive Systems and Floor StandingWhen not using the DC Choke a 5% input line reactor or line choke MUST be used.
Example: ATV630C22N4 includes a DC Choke ATV630C22N4MN does not include a DC Choke.
All Drive Systems and Floor Standing Products have as standard embedded line chokes and optional motor chokes.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.