What terminals are included in the Basic I/O Terminal Card for the Altivar 900 Process Drive?
Resolution:
Control Electronics – ATV900 Basic I/O-Terminal
- 8 digital inputs
- DI1, DI2...DI8
- DI7 and DI8
- Also frequency/pulse inputs
- 2 STO (Safe Torque Off) – SIL3
- STOA
- STOB
- 3 analog inputs
- AI1
- Configurable for voltage or current signal
- Also used as temperature input (PTC probe)
- Default as 0-10vdc
- AI2
- Configurable for voltage or (+/- voltage) signal
- Default as +/- (0-10vdc)
- AI3
- Configurable for voltage or current signal
- Also used as temperature input (PTC probe)
- Default as 4-20mA
- AI1
- 3 relays
- R1
- 1 normally opened set of contacts and 1 normally closed set of contacts
- R2
- 1 normally opened set of contacts
- R3
- 1 normally opened set of contacts
- R1
- 2 analog outputs
- AQ1
- AQ2
- 1 digital output
- DQ–
- DQ+
- Pulse output
- 4 RJ45 connectors for communication
- 1 Modbus RTU Port
- 2 Modbus TCP/Ethernet IP Port
- 1 Modbus HMI Port
Notes: The Altivar 600 Process Drive and removable connectors on its terminal card which is different from the Altivar 900 Process Drive. For the Altivar 900 Process Drive the complete board is removable
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.