What Communication Protocols and Fieldbus Options Are Available for Altivar Process ATV900 Series Drives?
Resolution:
Altivar Process ATV900 series drives provide integrated Ethernet and Modbus serial communication. Additional industrial networks can be supported through optional fieldbus modules.
Integrated Communication
The drive includes four RJ45 communication ports:
- 2 Ethernet ports: EtherNet/IP and Modbus TCP
- 2 serial ports: Modbus serial
The integrated Ethernet connection also supports features such as:
- Dual-port Ethernet for daisy-chain and ring network topologies
- RSTP for network redundancy
- SNMP for network diagnostics and management
- FDR (Fast Device Replacement) for device configuration replacement
- Embedded web server for monitoring, configuration, and diagnostics
- Connection to configuration tools such as SoMove
The Modbus serial connection can be used for communication with other Modbus devices, HMIs, and configuration tools.
Optional Fieldbus Communication
The ATV900 series also supports optional fieldbus modules for:
- CANopen
- RJ45 daisy chain (VW3A3608)
- Sub-D (VW3A3618)
- Screw terminal block (VW3A3628)
- EtherCAT (VW3A3601)
- PROFINET (VW3A3627 & VW3A3647)
- PROFIBUS DP V1 (VW3A3607)
- DeviceNet (VW3A3609)
The PROFINET and PROFIBUS DP V1 modules also support PROFIdrive and CiA402 profiles.
Additional Information
- Only one fieldbus communication module can be installed, using Slot A.
- Communication, monitoring, and diagnostics can remain available when the control section is supplied separately, even when the drive power section is not energized.
- The expansion slots can also accommodate compatible I/O and relay modules. Two modules of the same type cannot be installed simultaneously.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.