What are remedies for the Supply Mains Overvoltage Fault (OSF) on the Altivar Process Drive?
Resolution:
-
Check the incoming line voltage
- Measure the three-phase supply voltage feeding the drive.
- Verify that it is within the drive's specified voltage range.
-
Check for power factor correction capacitors
- Capacitor banks connected to the same power system can cause the line voltage to rise and may contribute to an OSF fault.
-
Measure the DC Bus Voltage
- Measure between terminals PA+ and PC-.
- On an ATV630, these terminals are located behind the black protective sticker.
-
Inspect for nearby regenerative or DC-generating equipment
- Other equipment connected to the same electrical system may be feeding energy back into the supply network and causing the DC bus voltage to rise.
-
Verify whether the installation uses an IT system
- Examples include High-Leg Delta or Corner-Grounded Delta systems.
- If present, Schneider recommends disconnecting the drive's EMI filter, power cycling the drive, and checking whether the fault returns.
-
Measure each incoming phase-to-ground voltage
- A high-leg condition can overcharge the EMI filter capacitors, which can in turn raise the DC bus voltage and trigger the OSF fault.