How do you set up the ATV312 for for Auto/Manual (HOA) Control?

Resolution:

The ATV312 can be configured for Auto/Manual (Hand-Off-Auto or HOA) control using a three-position selector switch. This setup allows the drive to switch between two different speed references, typically a manual speed command and an automatic process control signal.

Configuration Steps

1. Configure the Speed References (CTL Menu)

Set the following parameters:

  • Fr1 = AI1 → Manual speed reference
  • Fr2 = AI3 → Automatic speed reference
  • RFC = LI3 → Input used to switch between Fr1 and Fr2

When LI3 changes state, the drive switches between the manual and automatic speed references.

2. Disable Preset Speeds (FUN Menu)

To prevent preset speed functions from interfering with HOA operation, disable the preset speed parameters:

  • PS2 = No
  • PS4 = No

How It Works

  • Hand (Manual): The drive uses the speed reference assigned to AI1.
  • Off: The drive is stopped.
  • Auto: The drive uses the speed reference assigned to AI3.

This configuration allows a three-position HOA switch to select between manual operation, stop, and automatic operation.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.