Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What method of ground fault testing is recommended for circuit breakers?
Issue:
Ground fault testing of circuit breakers

Product Line:
Circuit Breakers

Resolution:
Schneider Electric recommends primary injection testing to comply with the requirements of NEC 230.95(C) for ground fault testing upon installation. Secondary injection testing may be done at the option of the customer for scheduled maintenance after the installation has been tested and commissioned.
For test procedures, please consult the Field Test and Maintenance Guide.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings