How can we help you today?
How do you set up the ATV320 drive so that the digital DO output controls output contactor command OCC?
Issue:
Set up the ATV320 drive so that the digital DO output controls output contactor command OCC.
Product Line:
ATV320
Environment:
All
Cause:
Wants to set up the DQ or DO so that it controls the a output for OCC.
Resolution:
Wiring:
Jumper +24vdc to DQ+
Wire your + side of your relay coil to DQ-
Wire the other side of the coil to Com
Programming:
In the Application Function Menu, set OCC to DO1
Set up the ATV320 drive so that the digital DO output controls output contactor command OCC.
Product Line:
ATV320
Environment:
All
Cause:
Wants to set up the DQ or DO so that it controls the a output for OCC.
Resolution:
Wiring:
Jumper +24vdc to DQ+
Wire your + side of your relay coil to DQ-
Wire the other side of the coil to Com
Programming:
In the Application Function Menu, set OCC to DO1
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.