Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
​Is there an adapter or mounting kit available, to allow a LA36400, LH36400, LDA, LGA, LJA, or LLA 400A breaker to be able to installed on the narrow side of a HCM,HCP,HCW, or HCRU panelboard?
Issue:
Adapter or mounting kit to allow a powerpact or legacy L frame 400A breaker to be able to be installed on the narrow side of an I-line panel

Product Line:
Panelboard

Environment:
I-line panel, HCM, HCP, HCW, HCRU

Cause:
Mounting a branch breaker in an I-line panel larger than 250A on the narrow side.

Resolution:
No. Circuit breakers larger than 250A can only be installed on the wide side of an I-line panel, or on a single row I-line panel like the HCP-SU.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings