How can we help you today?

Can MDGF be combined with ZSI?

Issue:
ZSI on MDGF systems

Product Line:
Circuit breakers

Resolution:
On MDGF systems:
  • In a Main-Tie-Main system, the main breaker cannot be short time ZSI restrained by the tie breaker.
  • Since the main circuit breaker cannot be restrained on short time, it must be ZSI self restrained on the short time function.
  • The main circuit breaker can be ground fault restrained by the feeder breakers.
  • Installation of GF ZSI has no effect on MDGF and MDGF has no effect on GF ZSI.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings