What is the maximum motor cable length for ATV660 drives?

Issue:
Is there a recommendation for the maximum motor cable length for ATV660 drives?

Product line:
Altivar ATV660

Environment:
All

Cause:
N/A

Resolution:
150 meters with shielded cable
250 meters with unshielded cable

300 meters with shielded cable and option "300m DV/DT filter"
500 meters with unshielded cable and option "300m DV/DT filter"

Schneider Electric USA