How do I setup Level Control on an Altivar 600 Process Drive?

Resolution:

The Level Control function in the Altivar 600 Process Drive is designed for water and wastewater applications that require automatic tank filling or emptying using pumps.

This feature helps prevent:

  • Tank overflow during filling operations
  • Complete tank emptying during drain or pumping operations

The Level Control function can:

  • Control the speed of one Variable Speed Pump (VSP)
  • Automatically stage and de-stage up to five additional pumps on ATV600 drives
  • Support Fixed Speed Pumps (FSPs) or additional Variable Speed Pumps (VSPs) in multi-pump applications

Multi-Drive Configuration Requirements

For multi-drive pump control applications, the following are required:

  • Altivar 600 firmware version 1.6 or later
  • VW3A3721 Multi-Drive Ethernet Communication Card
  • Standard Ethernet cables
  • Fixed IP address configuration for all connected drives

The Multi-Drive feature enables coordinated operation of multiple drives in Multi-Pump mode.

Additional Information

  • Step-by-step configuration instructions are available in the attached setup document.
  • The Level Control function is available only on Altivar 600 series drives.
  • This feature is not supported on Altivar 900 series drives.
  • Multi-drive applications require the VW3A3721 Multi-Drive Communication Card.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.