Video: How do I configure Plus/Minus speed control on an Altivar Process drive?

Article available in these languages:

Resolution:
This guide explains how to configure Plus/Minus (Increase/Decrease) speed control using digital inputs on Altivar Process drives.

Configuration Steps:

  1. Go to [Complete Settings] → [Command and Reference]
  2. Set [Freq Switch Assign] (rFC) to [Ref Freq Channel 2] (FR2)
  3. Set [Ref Freq Channel 2] (FR2) to [Ref Frequency via DI] (UPdt)
  4. Navigate to [Complete Settings] → [Generic Functions] → [+/- Speed]
  5. Assign a digital input to [+ Speed Assign] (USP)
  6. Assign a digital input to [- Speed Assign] (dSP)
  7. Assign a digital input to [Ref Frequency Save] (Str)

How It Works:

  • The + Speed input increases frequency while active.
  • The – Speed input decreases frequency while active.
  • The ACC (Acceleration) and DEC (Deceleration) settings determine how quickly the speed changes.

Example:
If ACC = 6 seconds on a 60 Hz drive, the speed increases at 10 Hz per second (60 Hz ÷ 6 s).

  • Increase ACC → slower speed change
  • Decrease ACC → faster speed change
  • The same principle applies to DEC for decreasing speed

Check the next video for an step by step walkthrough or reference the attached document for more information




If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.