Can you convert settings from an ATV32 or ATV312 program into an ATV320 using SoMove Software?

Article available in these languages:

Resolution:


Yes, SoMove software supports the conversion of configuration files from ATV32 and ATV312 drives to an ATV320.

Please follow the instruction steps below:

  1. Open Somove and from the Home Screen, click on [Device Conversion] button on the left under tools.
  2. Upload .psx ATV32 or ATV312 file that you want to convert.
  3. Select your Output device type from the list.
  4. Choose if you want the B suffix or the C suffix version ATV320 drive.
  5. Option window comes up to allow you to save changes to a new file.
  6. Save the new file and continue.
  7. After the conversion is complete, review the configuration and verify any parameters that may not have a direct equivalent due to differences in hardware, firmware, or available functions between drive families.

Recommendation: Always validate the converted settings and perform functional testing before commissioning the ATV320 to ensure the application operates as expected.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.