How can we help you today?

Can I use function block GMC.Control_ATV to control an ATV340 using a SoMachine PLC?

Issue:
Can I use function block GMC.Control_ATV to control an ATV340 using a SoMachine PLC?

Product Line:
SoMachine V4

Resolution:
You can use function block GMC.Control_ATV to control an ATV340 but you need to adjust the I/O mapping of the drive.
The I/O mapping of the drive can only be adjusted with the DTM commissioning software.
The library uses the assemblies 100 and 101 and requires the following mapping:
  • For assembly 100 (controller to drive):
    • First word: CMD (logic address 8501)
    • Second word: LFRD (logic address 8602)
  • For assembly 101 (drive to controller):
    • First word: ETA (logic address 3201)
    • Second word: FRRD (logic address 8604)
    • Third word: LCR (logic address 3204)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.