Can the ATV630 be powered using only a 24VDC control supply for parameter setup?

Resolution:

Yes. The Altivar Process ATV600 series (including the ATV630) can be powered using an external +24VDC control supply only.

To do this:

  • Connect the external +24VDC supply to terminal P24
  • Connect the external common to terminal 0V

This will power the control circuit and display (HMI), allowing you to:

  • Access the interface
  • Configure and modify parameters

The main power supply is not required for basic setup and programming.