How can we help you today?
ATV340 with the resolver card- what parameter is for the measured actual speed?
Resolution:
It is MMF (@3219) - units: [0.1Hz]
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.