Do you have to disconnect the EMC filter on the ATV600/900 using a Ungrounded Delta system?

Issue:
Disconnecting the EMC filter on the ATV600/900 using a Ungrounded Delta system.


Resolution:
Yes, The older version of the installation manual did not show Ungrounded Delta as a requirement, but that has been updated..
ATV600 series Installation Manual available here: https://www.se.com/us/en/download/document/EAV64301/
ATV900 series Installation Manual available here: https://www.se.com/us/en/download/document/NHA80932/
**

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.