Can additional neutral bars be added to I-line panels in the field?
Issue:
Can you field install a 200% neutral or add additional neutral bars to I-line panels?

Product Line:
HCM, HCP, HCPSU, HCRU, HCW, HCN I-line panelboards

Environment:
Products sold in North America

Resolution:
No, you cannot field install or modify the neutral capacity.  This would void the UL label.
The panel would need to be ordered factory installed with a 200% Neutral.  Adding the 200% rated neutral will double the terminal capacity in most cases.