How do I retrieve the value of a BOOL in a Vijeo Designer Script?
Issue:
How do I retrieve the value of a BOOL in a Vijeo Designer Script?
Product Line:
Vijeo Designer (all versions)
Resolution:
To retrieve the value of a BOOL in a Vijeo Designer Script, you need to use the following call:
Suppose we have a Vijeo Designer variable: BOOL01
The script call is:
BOOL01.getIntValue();
The result is going to be 0 or 1
To use the return value, you should declare an int and store the return value in it.