How to convert the Float 32 Format to decimal.

Issue:
User needs to convert a Float 32 register value into a decimal number

Product:
ION and Powerlogic Meters

Environment:
Arithmetic Conversion

Cause:
Some registers are stored as Float 32 values. In order to make sense of that value we have to convert that number to a decimal value.

Resolution:
Float 32 values will take 2 registers, if you check in the Register List.

  1. So, to start with convert the values separately in both the registers to Hexadecimal.
  2. Now, use the below link and use the value in the registers in ascending next to each ​​​​​​

https://www.h-schmidt.net/FloatConverter/IEEE754.html

Below is an example of the process:

For Registers,
3000 - 5EF3
3001 - 4323

Input the hexadecimal box of the link as 5EF34323 to get the exact decimal values. 8.7644463E18

Attached document screenshot for further reference.


Schneider Electric USA

Attachment(s)
IEEE 754 Converter.pdf [150.59 KB]