How can an ATV212 provide an alarm indicating a potential cooling fan or overheating issue before the drive faults?

While the ATV212 does not provide direct cooling fan status monitoring, it can provide an early warning of an overheating condition before an overtemperature fault occurs.

A flashing "L" on the drive keypad indicates that the drive is approaching an overheating condition. This warning can also be monitored through Modbus communications.

  • Function Code: FC91
  • Register: 64,657
  • Bit: 3 (Motor Overload Alarm)

By monitoring this bit, a PLC, SCADA system, or other controller can generate an alarm when the drive is nearing an overheating condition, allowing corrective action to be taken before the drive faults and causes downtime.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.