How can I configure my ATV630 drive to quickly ramp up to speed when a run command is issued and then operate in PID mode once up to speed?
Issue:
I need my pump motor to quickly accelerate to speed when starting, and then have PID enabled once up to speed.
Product Line:
ATV630 series drives and enclosed versions (660, 680 . . .)
Resolution:
Parameter "PID Acceleration time" under [Complete settings] [Pump functions] [PID controller] [Settings] can be used to achieve this function. Set your low speed setting (LSP) to the minimum speed your motor needs to run, then set the PID Acceleration time (ACCP) parameter to the number of seconds you want the drive to take to achieve full speed. (If you want the drive to reach 30 Hz. in 5 seconds, set ACCP to 10. ACCP is speed to 60.0Hz. 10 seconds to 60 Hz. = 5 seconds to 30 Hz.) The drive will then follow this acceleration rate until the LSP speed is attained, then switch over to PID mode and follow the 'PID RAMP" time while in PID mode.
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.