Video: How do you set up the basic parameters on an ATV320 drive?

Article available in these languages:

Resolution:

Setting up basic parameters on an ATV320 drive is done through the keypad by navigating the configuration menus. The most important settings are grouped in a few key sections.


⚙️ Basic Setup Steps

1. Simple Start Menu (CONF > FULL > SIM)

Use this menu for quick setup of essential drive parameters:

  • tFr – Maximum frequency
  • ItH – Motor thermal current (motor FLA)
  • ACC – Acceleration time (ramp up)
  • dEC – Deceleration time (ramp down)
  • LSP – Minimum speed
  • HSP – Maximum speed

👉 This menu is designed for fast commissioning with minimal configuration.


2. Motor Base Settings (CONF > FULL > drC)

Configure the motor’s base frequency:

  • bFr – Base motor frequency (typically 50 or 60 Hz)

👉 These settings define the fundamental operating characteristics of the motor. [2025_ATV32...Manual.pdf | PDF]


3. Motor Nameplate Parameters (CONF > FULL > drC > ASY)

Enter the motor data from the nameplate:

  • nPr – Motor power (HP or kW)
  • UnS – Rated motor voltage
  • nCr – Rated motor current (FLA)
  • FrS – Rated motor frequency
  • nSP – Rated motor speed (RPM)

👉 Accurate motor data is essential for proper performance and protection. [2025_ATV32...Manual.pdf | PDF]


4. Drive Settings (CONF > FULL > SET)

Adjust operating limits and protection:

  • CLI – Current limit
    • Set above motor FLA (typically up to 150%)

👉 This helps protect the drive and motor from overcurrent conditions.


⚠️ Important Note

Always program the drive using the motor nameplate values. This ensures accurate control, proper protection, and optimal performance.


For more details, refer to the ATV320 Programming Manual (NVE41295).



If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.