Running Reconfigure on a system that has been configured for SSL breaks the SSL configuration

Issue:

Running Reconfigure on a system that has been configured for SSL breaks the SSL configuration

Product Line:

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

PME

Cause:

Running Reconfigure on a system that has been configured for SSL breaks the SSL configuration

Resolution:

It is possible to configure PME to use SSL - see FA309041.
If this has been done, and then the installer is run in Configure mode, duplicate entries are created in the ..\WebServices\web.config file. See below:

<service name="PowerQuality.Analytics">
<endpoint binding="webHttpBinding" contract="PowerQuality.Analytics" behaviorConfiguration="RESTBehavior" bindingConfiguration="http" />
<!--<endpoint binding="webHttpBinding" contract="PowerQuality.Analytics" behaviorConfiguration="RESTBehavior" bindingConfiguration="https" />-->
</service>
<service name="PowerQuality.EventProcessor">
<endpoint binding="webHttpBinding" contract="PowerQuality.EventProcessor" behaviorConfiguration="RESTBehavior" bindingConfiguration="http" />
<!--<endpoint binding="webHttpBinding" contract="PowerQuality.EventProcessor" behaviorConfiguration="RESTBehavior" bindingConfiguration="https" />-->
</service>
<service name="PowerQuality.DowntimeService.Impact">
<endpoint binding="webHttpBinding" contract="PowerQuality.DowntimeService.Impact" behaviorConfiguration="RESTBehavior" bindingConfiguration="http" />
<!--<endpoint binding="webHttpBinding" contract="PowerQuality.DowntimeService.Impact" behaviorConfiguration="RESTBehavior" bindingConfiguration="https" />-->
</service>

Should this happen, it will not be possible to log into the Web Applications. To correct this, it is necessary to repeat the steps required to configure PME for SSL.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.