How are +/- speeds set up on the ATV32 or ATV320 Drive?
Issue:
Plus Minus Speed set up on ATV32 or ATV320 Drive.
Product Line:
ATV32, ATV320
Environment:
All
Cause:
NA
Resolution:
Set up the drive as follows:
Wire one side of your minus switch to the +24v terminal and the other side of the minus switch to a logic input (example DI5)
Wire one side of your plus switch to the +24v terminal and the other side of the plus switch to a logic input (example DI6)
Then program the drive as follows:
CTL menu:
RFC= Fr2 (Ref 2 switching set to Ch2 active)
FR2= UPdt (Ref 2 channel set to + and - speed control)
FUn menu:
UPd + /- speeds
USP= + speed input for DI5 or you can choose your logic input assignment.
dSP= - speed input for DI6 or you can choose your logic input assignment.
Plus Minus Speed set up on ATV32 or ATV320 Drive.
Product Line:
ATV32, ATV320
Environment:
All
Cause:
NA
Resolution:
Set up the drive as follows:
Wire one side of your minus switch to the +24v terminal and the other side of the minus switch to a logic input (example DI5)
Wire one side of your plus switch to the +24v terminal and the other side of the plus switch to a logic input (example DI6)
Then program the drive as follows:
CTL menu:
RFC= Fr2 (Ref 2 switching set to Ch2 active)
FR2= UPdt (Ref 2 channel set to + and - speed control)
FUn menu:
UPd + /- speeds
USP= + speed input for DI5 or you can choose your logic input assignment.
dSP= - speed input for DI6 or you can choose your logic input assignment.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.