What can cause an O1CT error in Somove?
Resolution:
Normally, this error occurs in SoMove when Option Card 1 installed in the drive is not compatible with the .PSX file being transferred. Verify that the hardware configuration of the target drive matches the configuration stored in the .PSX file, including any option cards and communication modules. If there is a mismatch between the file configuration and the actual hardware, SoMove may generate an O1CT error during the transfer process.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.